Sense-Ware UV/IR-210/1CZ Flame Detector SW1158
$ 2,300
SW1158
Sensitive to virtually all flame types
-
Dual-sensor UV/IR flame detector for high-reliability fire detection
-
10–28 VDC operating voltage with low power consumption
-
Manual fixed sensitivity setting for stable performance
-
Integrated latch alarm functionality for secure alerting
-
Explosion protection: ATEX II 3G Ex nA IIC T4 Gc / II 3D Ex tc IIIC T71°C Dc
-
Temperature range: -25°C to +70°C
-
Rugged white GRP (Glass-Reinforced Polyester) housing
-
Suitable for hydrogen and hydrocarbon flame detection
-
Automatic hourly self-test function ensures sensor reliability
-
Compatible with SM21 bracket (Part No. 2401228)
-
Relay output for both alarm and fault conditions
-
CPR-EN54-10 certified for flame detection safety standards
The Sense-Ware UV/IR-210/1CZ Flame Detector (P/N SW1158) is an advanced, dual-sensor flame detector combining ultraviolet (UV) and infrared (IR) detection technologies. It is engineered for environments where high reliability and false-alarm immunity are critical. This detector utilizes microprocessor-driven analysis to evaluate signals from both UV and IR channels—requiring both sensors to exceed their thresholds before triggering an alarm. This dual verification greatly reduces false alarms from sources like sunlight, arc welding, or hot objects.
Its GRP housing offers durability in industrial or outdoor settings, and the unit meets ATEX Zone 2 and Zone 22 hazardous area standards, making it ideal for industries such as chemical processing, power generation, and storage facilities. The device supports manual sensitivity configuration and provides a latched alarm output for fire events. Operating over a wide temperature range (-25°C to +70°C), it is robust even in challenging climates. Maintenance is simplified through automatic hourly self-testing, and a test lamp is available for manual end-to-end inspection.
Specification | Details |
---|---|
Model | UV/IR-210/1CZ |
Part Number | SW1158 |
Operating Voltage | 10–28 VDC |
Alarm Type | Latched |
Sensitivity | Fixed (Manual Set) |
Certifications | ATEX II 3G Ex nA IIC T4 Gc / II 3D Ex tc IIIC |
Temperature Range | -25°C to +70°C |
Material | GRP (White) |
Self-Test | Automatic every hour |
Alarm & Fault Relay | Included |
Mounting Accessory | SM21 Bracket (P/N: 2401228) |
Certification Standard | CPR-EN54-10 |
Application | Hydrogen and general hydrocarbon flame detection |